title: "Ask an electrical safety officer: I'm installing a natural gas stove. Is an outside-vented range hood mandatory or can I use a recirculating range hood? | Technical Safety BC"
description: Unless the installation instructions of the new range specifically require an exhaust hood vented to the outdoors, there is no other code requirement under the Gas Safety Regulation which requires a hood for a residential range.
image: https://blog.technicalsafetybc.ca/hubfs/Imported_Blog_Media/GasStove.jpg
---

[Skip to content](https://blog.technicalsafetybc.ca/ask-electrical-safety-officer-im-installing-natural-gas-stove-outside-vented-range-hood#main-content)

[![Technical Safety BC colour logo with gear](https://blog.technicalsafetybc.ca/hs-fs/hubfs/TSBC_Stacked_RGB%20300%20dpi%20-%20transparent%20background-1.png?width=600&height=179&name=TSBC_Stacked_RGB%20300%20dpi%20-%20transparent%20background-1.png "Technical Safety BC colour logo with gear")](https://www.technicalsafetybc.ca/)

[Visit main site](https://www.technicalsafetybc.ca/) [Contact us](https://www.technicalsafetybc.ca/contact/contact-us)

[Back to blog](https://blog.technicalsafetybc.ca/)

# Ask an electrical safety officer: I'm installing a natural gas stove. Is an outside-vented range hood mandatory or can I use a recirculating range hood?

 March 5, 2019

 1 Minute read

![](https://blog.technicalsafetybc.ca/hubfs/Imported_Blog_Media/GasStove.jpg)

 

## Q: I'm installing a natural gas stove. Is an outside-vented range hood mandatory or can I use a recirculating range hood?

Our safety officer says:

Unless the installation instructions of the new range specifically require an exhaust hood vented to the outdoors, there is no other code requirement under the Gas Safety Regulation which requires a hood for a residential range, although it is recommended. Also, the BC Building Code (which does not fall under the jurisdiction of Technical Safety BC) may have specific ventilation requirements.

Please consult your local building official for confirmation of the requirements within your jurisdiction.

 Share this article: 

[![Share on Facebook](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/facebook-blue.svg)](http://www.facebook.com/share.php?u=https%3A%2F%2Fblog.technicalsafetybc.ca%2Fask-electrical-safety-officer-im-installing-natural-gas-stove-outside-vented-range-hood%3Futm_medium%3Dsocial%26utm_source%3Dfacebook) [![Share on LinkedIn](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/linkedin-blue.svg)](http://www.linkedin.com/shareArticle?mini=true&url=https%3A%2F%2Fblog.technicalsafetybc.ca%2Fask-electrical-safety-officer-im-installing-natural-gas-stove-outside-vented-range-hood%3Futm_medium%3Dsocial%26utm_source%3Dlinkedin) [![Share on Twitter](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/twitter-blue.svg)](https://twitter.com/intent/tweet?original_referer=https%3A%2F%2Fblog.technicalsafetybc.ca%2Fask-electrical-safety-officer-im-installing-natural-gas-stove-outside-vented-range-hood%3Futm_medium%3Dsocial%26utm_source%3Dtwitter&url=https%3A%2F%2Fblog.technicalsafetybc.ca%2Fask-electrical-safety-officer-im-installing-natural-gas-stove-outside-vented-range-hood%3Futm_medium%3Dsocial%26utm_source%3Dtwitter&source=tweetbutton&text=Ask%20an%20electrical%20safety%20officer%3A%20I%27m%20installing%20a%20natural%20gas%20stove.%20Is%20an%20outside-vented%20range%20hood%20mandatory%20or%20can%20I%20use%20a%20recirculating%20range%20hood%3F%20%7C%20Technical%20Safety%20BC) [![Share on Email](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/email-blue.svg)](mailto:?subject=Check%20out%20https%3A%2F%2Fblog.technicalsafetybc.ca%2Fask-electrical-safety-officer-im-installing-natural-gas-stove-outside-vented-range-hood%3Futm_medium%3Dsocial%26utm_source%3Demail%20&body=Check%20out%20https%3A%2F%2Fblog.technicalsafetybc.ca%2Fask-electrical-safety-officer-im-installing-natural-gas-stove-outside-vented-range-hood%3Futm_medium%3Dsocial%26utm_source%3Demail)

## Subscribe for safety updates and insights

## Browse topics

- [Homeowner](https://blog.technicalsafetybc.ca/tag/homeowner)
- [Gas](https://blog.technicalsafetybc.ca/tag/gas)
- [Contractor](https://blog.technicalsafetybc.ca/tag/contractor)
- [Electrical](https://blog.technicalsafetybc.ca/tag/electrical)
- [Asset Owner](https://blog.technicalsafetybc.ca/tag/asset-owner)
- [Ask A Safety Officer](https://blog.technicalsafetybc.ca/tag/ask-a-safety-officer)
- [Homeowner Safety](https://blog.technicalsafetybc.ca/tag/homeowner-safety)
- [Passenger Ropeways](https://blog.technicalsafetybc.ca/tag/passenger-ropeways)
- [Boiler, PV and Refrigeration](https://blog.technicalsafetybc.ca/tag/boiler-pv-and-refrigeration)
- [Carbon Monoxide](https://blog.technicalsafetybc.ca/tag/carbon-monoxide)
- [Public Safety](https://blog.technicalsafetybc.ca/tag/public-safety)
- [Amusement Devices](https://blog.technicalsafetybc.ca/tag/amusement-devices)
- [Elevating Devices](https://blog.technicalsafetybc.ca/tag/elevating-devices)
- [Railways](https://blog.technicalsafetybc.ca/tag/railways)
- [Alternative Safety Approaches](https://blog.technicalsafetybc.ca/tag/alternative-safety-approaches)
- [CO Alarm](https://blog.technicalsafetybc.ca/tag/co-alarm)
- [Client Support](https://blog.technicalsafetybc.ca/tag/client-support)
- [Smarter Safety](https://blog.technicalsafetybc.ca/tag/smarter-safety)
- [FSR](https://blog.technicalsafetybc.ca/tag/fsr)
- [Camping](https://blog.technicalsafetybc.ca/tag/camping)
- [Chairlift](https://blog.technicalsafetybc.ca/tag/chairlift)
- [Corporate news](https://blog.technicalsafetybc.ca/tag/corporate-news)
- [RV safety](https://blog.technicalsafetybc.ca/tag/rv-safety)
- [Skiing](https://blog.technicalsafetybc.ca/tag/skiing)
- [Travel](https://blog.technicalsafetybc.ca/tag/travel)
- [Vacation](https://blog.technicalsafetybc.ca/tag/vacation)
- [extreme heat](https://blog.technicalsafetybc.ca/tag/extreme-heat)
- [snowboarding](https://blog.technicalsafetybc.ca/tag/snowboarding)

## Related articles

![](https://blog.technicalsafetybc.ca/hs-fs/hubfs/Imported_Blog_Media/Row%20of%20caravan%20trailers%20_0.jpg?width=352&name=Row%20of%20caravan%20trailers%20_0.jpg)

### Ask a gas safety officer: What type of permit is required for a mobile camp?

 December 12, 2018

 1 Minute read

 Mobile camps may consist of relocatable structures consisting of multiple certified mobile trailers/manufactured buildings which are not considered certified mobile homes. They are considered as a unit and require a commercial installation permit per unit.

[Read More](https://blog.technicalsafetybc.ca/blog/ask-gas-safety-officer-what-type-permit-required-mobile-camp?hsLang=en)

![](https://blog.technicalsafetybc.ca/hs-fs/hubfs/Imported_Blog_Media/pexels-photo-14167_web.jpg?width=352&name=pexels-photo-14167_web.jpg)

### Ask an electrical safety officer: Is a permit needed to install or replace a light fixture?

 December 20, 2018

 1 Minute read

 Permits are required to install any permanently-installed light fixture. Learn more here.

[Read More](https://blog.technicalsafetybc.ca/ask-electrical-safety-officer-permit-needed-install-or-replace-light-fixture?hsLang=en)

![](https://blog.technicalsafetybc.ca/hs-fs/hubfs/Imported_Blog_Media/pjoseph_20180321_0501_smaller.jpg?width=352&name=pjoseph_20180321_0501_smaller.jpg)

### Ask a Gas Safety Officer: What Inspections Are Required for a Contractor Installing or Replacing Gas Appliances?

 December 12, 2018

 3 Minute read

 Gas Safety Regulation requires the holder of a permit, or the gas fitter that represents the holder of the permit, to notify Technical Safety BC that regulated work has been performed.

[Read More](https://blog.technicalsafetybc.ca/ask-gas-safety-officer-what-inspections-are-required-contractor-installing-or-replacing-gas?hsLang=en)

Back to top

[Report an incident](https://portal.technicalsafetybc.ca/report-incident/incident-reporting-form)

[Contact us](https://www.technicalsafetybc.ca/contact/contact-us)

As a province-wide organization, Technical Safety BC respectfully recognizes that its employees live and work on the traditional and unceded territories of the many Indigenous Nations that have thrived throughout British Columbia since time immemorial.

[© 2026 Technical Safety BC](https://www.technicalsafetybc.ca/)

- [Cookie Policy](https://www.technicalsafetybc.ca/cookie-policy)
- [Privacy Policy](https://www.technicalsafetybc.ca/privacy-policy)
- [Terms of Use](https://www.technicalsafetybc.ca/terms-use)

<https://www.instagram.com/technicalsafetybc/?hl=en>

<https://twitter.com/techsafetybc?lang=en>

<https://ca.linkedin.com/company/technical-safety-bc>

<https://www.facebook.com/technicalsafetyBC/>

```json
{
  "@context" : "https://schema.org",
  "@type" : "BlogPosting",
  "author" : {
    "@type" : "Person",
    "name" : "Technical Safety BC",
    "url" : "https://blog.technicalsafetybc.ca/author/technical-safety-bc"
  },
  "dateModified" : "2022-12-21T23:29:16.562Z",
  "datePublished" : "2019-03-05T08:00:00.000Z",
  "headline" : "Ask an electrical safety officer: I'm installing a natural gas stove. Is an outside-vented range hood mandatory or can I use a recirculating range hood? | Technical Safety BC",
  "image" : [ "https://blog.technicalsafetybc.ca/hubfs/Imported_Blog_Media/GasStove.jpg" ],
  "mainEntityOfPage" : {
    "@id" : "https://blog.technicalsafetybc.ca/ask-electrical-safety-officer-im-installing-natural-gas-stove-outside-vented-range-hood",
    "@type" : "WebPage"
  },
  "publisher" : {
    "@type" : "Organization",
    "logo" : {
      "@type" : "ImageObject",
      "url" : "https://blog.technicalsafetybc.ca/hubfs/TSBC_Stacked_RGB%20300%20dpi%20-%20transparent%20background-1.png"
    },
    "name" : "Technical Safety BC"
  }
}
```