title: "Ask a Gas Safety Officer: Why Does Gas Piping Need to Be Bonded? | Technical Safety BC"
description: ​​​​​​​Electrical bonding is the practice of intentionally electrically connecting all exposed metallic items not designed to carry electricity in a room or building as protection from electric shock.
image: https://blog.technicalsafetybc.ca/hubfs/Imported_Blog_Media/damaged%20csst%20with%20hole.jpg
---

[Skip to content](https://blog.technicalsafetybc.ca/blog/ask-gas-safety-officer-why-does-gas-piping-need-be-bonded#main-content)

[![Technical Safety BC colour logo with gear](https://blog.technicalsafetybc.ca/hs-fs/hubfs/TSBC_Stacked_RGB%20300%20dpi%20-%20transparent%20background-1.png?width=600&height=179&name=TSBC_Stacked_RGB%20300%20dpi%20-%20transparent%20background-1.png "Technical Safety BC colour logo with gear")](https://www.technicalsafetybc.ca/)

[Visit main site](https://www.technicalsafetybc.ca/) [Contact us](https://www.technicalsafetybc.ca/contact/contact-us)

[Back to blog](https://blog.technicalsafetybc.ca/)

# Ask a Gas Safety Officer: Why Does Gas Piping Need to Be Bonded?

 November 5, 2018

 1 Minute read

![](https://blog.technicalsafetybc.ca/hubfs/Imported_Blog_Media/damaged%20csst%20with%20hole.jpg)

## Q: Why does gas piping need to be bonded?

Electrical bonding is the practice of intentionally electrically connecting all exposed metallic items not designed to carry electricity in a room or building as protection from [electric shock](https://en.wikipedia.org/wiki/Electric_shock). If a failure of electrical insulation occurs, all bonded metal objects in the room will have substantially the same electrical potential, so that an occupant of the room cannot touch two objects with significantly different potentials. Even if the connection to a distant earth ground is lost, the occupant will be protected from dangerous [potential differences](https://en.wikipedia.org/wiki/Potential_difference).

Gas piping systems are required to be bonded by the B149.1 Natural Gas and Propane Installation code, as well as the C22.1 Canadian Electrical code (adopted as BC Electrical Code). The bonding is intended to not only protect the occupants from a potential electrical difference between two metallic surfaces, but also to protect the piping. As shown in the photo above, arcing created by a potential difference in a fault situation can damage piping or tubing systems creating a possible uncontrolled escape of gas from the system.

 Share this article: 

[![Share on Facebook](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/facebook-blue.svg)](http://www.facebook.com/share.php?u=https%3A%2F%2Fblog.technicalsafetybc.ca%2Fblog%2Fask-gas-safety-officer-why-does-gas-piping-need-be-bonded%3Futm_medium%3Dsocial%26utm_source%3Dfacebook) [![Share on LinkedIn](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/linkedin-blue.svg)](http://www.linkedin.com/shareArticle?mini=true&url=https%3A%2F%2Fblog.technicalsafetybc.ca%2Fblog%2Fask-gas-safety-officer-why-does-gas-piping-need-be-bonded%3Futm_medium%3Dsocial%26utm_source%3Dlinkedin) [![Share on Twitter](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/twitter-blue.svg)](https://twitter.com/intent/tweet?original_referer=https%3A%2F%2Fblog.technicalsafetybc.ca%2Fblog%2Fask-gas-safety-officer-why-does-gas-piping-need-be-bonded%3Futm_medium%3Dsocial%26utm_source%3Dtwitter&url=https%3A%2F%2Fblog.technicalsafetybc.ca%2Fblog%2Fask-gas-safety-officer-why-does-gas-piping-need-be-bonded%3Futm_medium%3Dsocial%26utm_source%3Dtwitter&source=tweetbutton&text=Ask%20a%20Gas%20Safety%20Officer%3A%20Why%20Does%20Gas%20Piping%20Need%20to%20Be%20Bonded%3F%20%7C%20Technical%20Safety%20BC) [![Share on Email](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/email-blue.svg)](mailto:?subject=Check%20out%20https%3A%2F%2Fblog.technicalsafetybc.ca%2Fblog%2Fask-gas-safety-officer-why-does-gas-piping-need-be-bonded%3Futm_medium%3Dsocial%26utm_source%3Demail%20&body=Check%20out%20https%3A%2F%2Fblog.technicalsafetybc.ca%2Fblog%2Fask-gas-safety-officer-why-does-gas-piping-need-be-bonded%3Futm_medium%3Dsocial%26utm_source%3Demail)

## Subscribe for safety updates and insights

## Browse topics

- [Homeowner](https://blog.technicalsafetybc.ca/tag/homeowner)
- [Gas](https://blog.technicalsafetybc.ca/tag/gas)
- [Contractor](https://blog.technicalsafetybc.ca/tag/contractor)
- [Electrical](https://blog.technicalsafetybc.ca/tag/electrical)
- [Asset Owner](https://blog.technicalsafetybc.ca/tag/asset-owner)
- [Ask A Safety Officer](https://blog.technicalsafetybc.ca/tag/ask-a-safety-officer)
- [Homeowner Safety](https://blog.technicalsafetybc.ca/tag/homeowner-safety)
- [Passenger Ropeways](https://blog.technicalsafetybc.ca/tag/passenger-ropeways)
- [Boiler, PV and Refrigeration](https://blog.technicalsafetybc.ca/tag/boiler-pv-and-refrigeration)
- [Carbon Monoxide](https://blog.technicalsafetybc.ca/tag/carbon-monoxide)
- [Public Safety](https://blog.technicalsafetybc.ca/tag/public-safety)
- [Amusement Devices](https://blog.technicalsafetybc.ca/tag/amusement-devices)
- [Elevating Devices](https://blog.technicalsafetybc.ca/tag/elevating-devices)
- [Railways](https://blog.technicalsafetybc.ca/tag/railways)
- [Alternative Safety Approaches](https://blog.technicalsafetybc.ca/tag/alternative-safety-approaches)
- [CO Alarm](https://blog.technicalsafetybc.ca/tag/co-alarm)
- [Client Support](https://blog.technicalsafetybc.ca/tag/client-support)
- [Smarter Safety](https://blog.technicalsafetybc.ca/tag/smarter-safety)
- [FSR](https://blog.technicalsafetybc.ca/tag/fsr)
- [Camping](https://blog.technicalsafetybc.ca/tag/camping)
- [Chairlift](https://blog.technicalsafetybc.ca/tag/chairlift)
- [Corporate news](https://blog.technicalsafetybc.ca/tag/corporate-news)
- [RV safety](https://blog.technicalsafetybc.ca/tag/rv-safety)
- [Skiing](https://blog.technicalsafetybc.ca/tag/skiing)
- [Travel](https://blog.technicalsafetybc.ca/tag/travel)
- [Vacation](https://blog.technicalsafetybc.ca/tag/vacation)
- [extreme heat](https://blog.technicalsafetybc.ca/tag/extreme-heat)
- [snowboarding](https://blog.technicalsafetybc.ca/tag/snowboarding)

## Related articles

![](https://blog.technicalsafetybc.ca/hs-fs/hubfs/Imported_Blog_Media/burn%20awarness%20blog-4.png?width=352&name=burn%20awarness%20blog-4.png)

### Ask a safety officer: how to prevent electrical fires

 February 11, 2021

 4 Minute read

 Burn Awareness Week this year is about electrical fires. Our electrical safety officer answers common questions about preventing electrical fires in the home.

[Read More](https://blog.technicalsafetybc.ca/ask-a-safety-officer-how-to-prevent-electrical-fires?hsLang=en)

![](https://blog.technicalsafetybc.ca/hs-fs/hubfs/Imported_Blog_Media/Electrical%20safety%20home_0.jpg?width=352&name=Electrical%20safety%20home_0.jpg)

### Ask a Safety Officer: Home office electrical safety

 October 18, 2021

 2 Minute read

 Our electrical safety officer covers common home office electrical hazards, and how to avoid them.

[Read More](https://blog.technicalsafetybc.ca/ask-safety-officer-home-office-electrical-safety?hsLang=en)

![](https://blog.technicalsafetybc.ca/hs-fs/hubfs/Imported_Blog_Media/iStock-481633162-2.jpg?width=352&name=iStock-481633162-2.jpg)

### Your home electrical safety checklist

 October 27, 2021

 5 Minute read

 Conduct an electrical safety check in your home today. Use our list to identify overlooked electrical hazards that could be dangerous in your home.

[Read More](https://blog.technicalsafetybc.ca/your-home-electrical-safety-checklist?hsLang=en)

Back to top

[Report an incident](https://portal.technicalsafetybc.ca/report-incident/incident-reporting-form)

[Contact us](https://www.technicalsafetybc.ca/contact/contact-us)

As a province-wide organization, Technical Safety BC respectfully recognizes that its employees live and work on the traditional and unceded territories of the many Indigenous Nations that have thrived throughout British Columbia since time immemorial.

[© 2026 Technical Safety BC](https://www.technicalsafetybc.ca/)

- [Cookie Policy](https://www.technicalsafetybc.ca/cookie-policy)
- [Privacy Policy](https://www.technicalsafetybc.ca/privacy-policy)
- [Terms of Use](https://www.technicalsafetybc.ca/terms-use)

<https://www.instagram.com/technicalsafetybc/?hl=en>

<https://twitter.com/techsafetybc?lang=en>

<https://ca.linkedin.com/company/technical-safety-bc>

<https://www.facebook.com/technicalsafetyBC/>

```json
{
  "@context" : "https://schema.org",
  "@type" : "BlogPosting",
  "author" : {
    "@type" : "Person",
    "name" : "Technical Safety BC",
    "url" : "https://blog.technicalsafetybc.ca/author/technical-safety-bc"
  },
  "dateModified" : "2023-12-19T23:46:17.672Z",
  "datePublished" : "2018-11-05T08:00:00.000Z",
  "headline" : "Ask a Gas Safety Officer: Why Does Gas Piping Need to Be Bonded? | Technical Safety BC",
  "image" : [ "https://blog.technicalsafetybc.ca/hubfs/Imported_Blog_Media/damaged%20csst%20with%20hole.jpg" ],
  "mainEntityOfPage" : {
    "@id" : "https://blog.technicalsafetybc.ca/blog/ask-gas-safety-officer-why-does-gas-piping-need-be-bonded",
    "@type" : "WebPage"
  },
  "publisher" : {
    "@type" : "Organization",
    "logo" : {
      "@type" : "ImageObject",
      "url" : "https://blog.technicalsafetybc.ca/hubfs/TSBC_Stacked_RGB%20300%20dpi%20-%20transparent%20background-1.png"
    },
    "name" : "Technical Safety BC"
  }
}
```