title: "Ask an electrical safety officer: Is installation of an electrical outlet inside a drawer permitted? | Technical Safety BC"
description: In general, the BC Electrical Code does not allow the use of receptacles in cupboards and drawers. However, there are some exceptions. Learn more!
image: https://blog.technicalsafetybc.ca/hubfs/Imported_Blog_Media/DockingDrawer_Permitted_0.jpg
---

[Skip to content](https://blog.technicalsafetybc.ca/blog/ask-electrical-safety-officer-installation-electrical-outlet-inside-drawer-permitted#main-content)

[![Technical Safety BC colour logo with gear](https://blog.technicalsafetybc.ca/hs-fs/hubfs/TSBC_Stacked_RGB%20300%20dpi%20-%20transparent%20background-1.png?width=600&height=179&name=TSBC_Stacked_RGB%20300%20dpi%20-%20transparent%20background-1.png "Technical Safety BC colour logo with gear")](https://www.technicalsafetybc.ca/)

[Visit main site](https://www.technicalsafetybc.ca/) [Contact us](https://www.technicalsafetybc.ca/contact/contact-us)

[Back to blog](https://blog.technicalsafetybc.ca/)

# Ask an electrical safety officer: Is installation of an electrical outlet inside a drawer permitted?

 March 6, 2019

 1 Minute read

![](https://blog.technicalsafetybc.ca/hubfs/Imported_Blog_Media/DockingDrawer_Permitted_0.jpg)

In general, the BC Electrical Code does not allow the use of receptacles in cupboards and drawers. However, there are some exceptions in rule 26-710 (h) & (i) such as microwave ovens, in line water heaters, and garbage disposal units. 

There are some USB-only charging outlets which may be installed as long as they are approved for use in Canada.

For example, the product shown above is certified for use in Canada. The best thing to do is always confirm that the product you are installing or having installed has a manufacturer’s approval label indicating it is approved for use in Canada. Refer to this [bulletin](https://www.technicalsafetybc.ca/regulatory-resources/regulatory-notices/approved-certification-marks-electrical-products) showing the approved certification marks for electrical products.

 Share this article: 

[![Share on Facebook](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/facebook-blue.svg)](http://www.facebook.com/share.php?u=https%3A%2F%2Fblog.technicalsafetybc.ca%2Fblog%2Fask-electrical-safety-officer-installation-electrical-outlet-inside-drawer-permitted%3Futm_medium%3Dsocial%26utm_source%3Dfacebook) [![Share on LinkedIn](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/linkedin-blue.svg)](http://www.linkedin.com/shareArticle?mini=true&url=https%3A%2F%2Fblog.technicalsafetybc.ca%2Fblog%2Fask-electrical-safety-officer-installation-electrical-outlet-inside-drawer-permitted%3Futm_medium%3Dsocial%26utm_source%3Dlinkedin) [![Share on Twitter](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/twitter-blue.svg)](https://twitter.com/intent/tweet?original_referer=https%3A%2F%2Fblog.technicalsafetybc.ca%2Fblog%2Fask-electrical-safety-officer-installation-electrical-outlet-inside-drawer-permitted%3Futm_medium%3Dsocial%26utm_source%3Dtwitter&url=https%3A%2F%2Fblog.technicalsafetybc.ca%2Fblog%2Fask-electrical-safety-officer-installation-electrical-outlet-inside-drawer-permitted%3Futm_medium%3Dsocial%26utm_source%3Dtwitter&source=tweetbutton&text=Ask%20an%20electrical%20safety%20officer%3A%20Is%20installation%20of%20an%20electrical%20outlet%20inside%20a%20drawer%20permitted%3F%20%7C%20Technical%20Safety%20BC) [![Share on Email](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/email-blue.svg)](mailto:?subject=Check%20out%20https%3A%2F%2Fblog.technicalsafetybc.ca%2Fblog%2Fask-electrical-safety-officer-installation-electrical-outlet-inside-drawer-permitted%3Futm_medium%3Dsocial%26utm_source%3Demail%20&body=Check%20out%20https%3A%2F%2Fblog.technicalsafetybc.ca%2Fblog%2Fask-electrical-safety-officer-installation-electrical-outlet-inside-drawer-permitted%3Futm_medium%3Dsocial%26utm_source%3Demail)

## Subscribe for safety updates and insights

## Browse topics

- [Homeowner](https://blog.technicalsafetybc.ca/tag/homeowner)
- [Gas](https://blog.technicalsafetybc.ca/tag/gas)
- [Contractor](https://blog.technicalsafetybc.ca/tag/contractor)
- [Electrical](https://blog.technicalsafetybc.ca/tag/electrical)
- [Asset Owner](https://blog.technicalsafetybc.ca/tag/asset-owner)
- [Ask A Safety Officer](https://blog.technicalsafetybc.ca/tag/ask-a-safety-officer)
- [Homeowner Safety](https://blog.technicalsafetybc.ca/tag/homeowner-safety)
- [Passenger Ropeways](https://blog.technicalsafetybc.ca/tag/passenger-ropeways)
- [Boiler, PV and Refrigeration](https://blog.technicalsafetybc.ca/tag/boiler-pv-and-refrigeration)
- [Carbon Monoxide](https://blog.technicalsafetybc.ca/tag/carbon-monoxide)
- [Public Safety](https://blog.technicalsafetybc.ca/tag/public-safety)
- [Amusement Devices](https://blog.technicalsafetybc.ca/tag/amusement-devices)
- [Elevating Devices](https://blog.technicalsafetybc.ca/tag/elevating-devices)
- [Railways](https://blog.technicalsafetybc.ca/tag/railways)
- [Alternative Safety Approaches](https://blog.technicalsafetybc.ca/tag/alternative-safety-approaches)
- [CO Alarm](https://blog.technicalsafetybc.ca/tag/co-alarm)
- [Client Support](https://blog.technicalsafetybc.ca/tag/client-support)
- [Smarter Safety](https://blog.technicalsafetybc.ca/tag/smarter-safety)
- [FSR](https://blog.technicalsafetybc.ca/tag/fsr)
- [Camping](https://blog.technicalsafetybc.ca/tag/camping)
- [Chairlift](https://blog.technicalsafetybc.ca/tag/chairlift)
- [Corporate news](https://blog.technicalsafetybc.ca/tag/corporate-news)
- [RV safety](https://blog.technicalsafetybc.ca/tag/rv-safety)
- [Skiing](https://blog.technicalsafetybc.ca/tag/skiing)
- [Travel](https://blog.technicalsafetybc.ca/tag/travel)
- [Vacation](https://blog.technicalsafetybc.ca/tag/vacation)
- [extreme heat](https://blog.technicalsafetybc.ca/tag/extreme-heat)
- [snowboarding](https://blog.technicalsafetybc.ca/tag/snowboarding)

## Related articles

![](https://blog.technicalsafetybc.ca/hs-fs/hubfs/Imported_Blog_Media/Electrical%20safety%20home_0.jpg?width=352&name=Electrical%20safety%20home_0.jpg)

### Ask a Safety Officer: Home office electrical safety

 October 18, 2021

 2 Minute read

 Our electrical safety officer covers common home office electrical hazards, and how to avoid them.

[Read More](https://blog.technicalsafetybc.ca/ask-safety-officer-home-office-electrical-safety?hsLang=en)

![](https://blog.technicalsafetybc.ca/hs-fs/hubfs/Imported_Blog_Media/iStock-481633162-2.jpg?width=352&name=iStock-481633162-2.jpg)

### Your home electrical safety checklist

 October 27, 2021

 5 Minute read

 Conduct an electrical safety check in your home today. Use our list to identify overlooked electrical hazards that could be dangerous in your home.

[Read More](https://blog.technicalsafetybc.ca/your-home-electrical-safety-checklist?hsLang=en)

![](https://blog.technicalsafetybc.ca/hs-fs/hubfs/Imported_Blog_Media/Outdoor%20electrical%20safety-1.jpg?width=352&name=Outdoor%20electrical%20safety-1.jpg)

### Ask a Safety Officer: Outdoor electrical safety

 October 15, 2021

 3 Minute read

 Looking to renovate your outdoor living space? Our electrical safety officer covers common outdoor electrical safety hazards and how to avoid them.

[Read More](https://blog.technicalsafetybc.ca/ask-safety-officer-outdoor-electrical-safety?hsLang=en)

Back to top

[Report an incident](https://portal.technicalsafetybc.ca/report-incident/incident-reporting-form)

[Contact us](https://www.technicalsafetybc.ca/contact/contact-us)

As a province-wide organization, Technical Safety BC respectfully recognizes that its employees live and work on the traditional and unceded territories of the many Indigenous Nations that have thrived throughout British Columbia since time immemorial.

[© 2026 Technical Safety BC](https://www.technicalsafetybc.ca/)

- [Cookie Policy](https://www.technicalsafetybc.ca/cookie-policy)
- [Privacy Policy](https://www.technicalsafetybc.ca/privacy-policy)
- [Terms of Use](https://www.technicalsafetybc.ca/terms-use)

<https://www.instagram.com/technicalsafetybc/?hl=en>

<https://twitter.com/techsafetybc?lang=en>

<https://ca.linkedin.com/company/technical-safety-bc>

<https://www.facebook.com/technicalsafetyBC/>

```json
{
  "@context" : "https://schema.org",
  "@type" : "BlogPosting",
  "author" : {
    "@type" : "Person",
    "name" : "Technical Safety BC",
    "url" : "https://blog.technicalsafetybc.ca/author/technical-safety-bc"
  },
  "dateModified" : "2022-12-14T02:33:01.372Z",
  "datePublished" : "2019-03-06T08:00:00.000Z",
  "headline" : "Ask an electrical safety officer: Is installation of an electrical outlet inside a drawer permitted? | Technical Safety BC",
  "image" : [ "https://blog.technicalsafetybc.ca/hubfs/Imported_Blog_Media/DockingDrawer_Permitted_0.jpg" ],
  "mainEntityOfPage" : {
    "@id" : "https://blog.technicalsafetybc.ca/blog/ask-electrical-safety-officer-installation-electrical-outlet-inside-drawer-permitted",
    "@type" : "WebPage"
  },
  "publisher" : {
    "@type" : "Organization",
    "logo" : {
      "@type" : "ImageObject",
      "url" : "https://blog.technicalsafetybc.ca/hubfs/TSBC_Stacked_RGB%20300%20dpi%20-%20transparent%20background-1.png"
    },
    "name" : "Technical Safety BC"
  }
}
```