[![Technical Safety BC colour logo with gear](https://blog.technicalsafetybc.ca/hs-fs/hubfs/TSBC_Stacked_RGB%20300%20dpi%20-%20transparent%20background-1.png?width=600&height=179&name=TSBC_Stacked_RGB%20300%20dpi%20-%20transparent%20background-1.png "Technical Safety BC colour logo with gear")](https://www.technicalsafetybc.ca/)

[Visit main site](https://www.technicalsafetybc.ca/) [Contact us](https://www.technicalsafetybc.ca/contact/contact-us)

[Back to blog](https://blog.technicalsafetybc.ca/)

# 9 Refrigeration Safety Tips

 November 19, 2018

 4 Minute read

![](https://blog.technicalsafetybc.ca/hubfs/Imported_Blog_Media/shutterstock_603039644-1.jpg)

While keeping food at an appropriate temperature in storage or transit is an obvious reason for maintaining an effective refrigeration system, careful attention must also be given to the potential safety risks associated with the use of ammonia as refrigerant.

Below are 9 tips to help keep refrigeration system users safe.

1. Implement a refrigeration system maintenance program that addresses: wear-out / end-of-life; resources and approval & accountability.
2. Provide refrigeration system, maintenance program and worker qualification/skill awareness training to all employees and representatives responsible or involved with approving arena maintenance related activities or expenses.
3. Implement clear procedures that provide guidance and instructions to employees regarding the hazards associated with leaking chillers and required actions.
4. Implement training and procedures for refrigeration system managers to identify the limitations of different technical qualifications associated with refrigeration systems and engage independent advisors for items considered a cause for concern.
5. Incorporate safety risk assessments into asset management planning activities for all arena and curling refrigeration systems and mechanical rooms.
6. Conduct an assessment of the organizational design and assigned resourcing for positions that are accountable for technical system management.
7. Conduct an assessment and test of ventilation systems to evaluate effective internal ventilation of the mechanical room and external discharge in a manner that minimizes risk of exposure.
8. Inspect all emergency discharge piping and confirm that routing does not enter any spaces that present a risk to public safety.
9. Make the following information (associated with management and oversight of regulated refrigeration systems) publicly available, if you manage public assembly facilities (such as arenas):

- - related capital budgeting plans for supporting maintenance programs;
    - assessment and audit criteria;
    - refrigeration system maintenance programs for regulated equipment;
    - results of assessments and audits;
    - independent recommendations relating to the condition of equipment, including recommendations from maintenance contractors for repair or replacement; and,
    - any other information relevant to the assessment, audits and overall safety of the technical equipment and its management programs.
      
      ![Thumbnail](https://blog.technicalsafetybc.ca/hs-fs/hubfs/Imported_Blog_Media/shutterstock_603039644-1.jpg?width=1000&height=668&name=shutterstock_603039644-1.jpg "industrial refrigeration")
      
      These nine recommendations are part of the 18 recommendations Technical Safety BC has made to improve safety in ice rink refrigeration systems and prevent an incident similar to the fatal ammonia release event that occurred at the Fernie Memorial Arena on October 17, 2017. The incident at Fernie tragically resulted in three fatalities, as well as the evacuation of 95 residents from 55 nearby homes. 
      
      The recommendations are based on the findings from Technical Safety BC’s [investigation](https://www.technicalsafetybc.ca/fernieincident) into the Fernie incident.
      
      <https://blog.technicalsafetybc.ca/blog/study-identifies-3-factors-behind-electric-shock?hsLang=en>

 

 Share this article: 

[![Share on Facebook](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/facebook-blue.svg)](http://www.facebook.com/share.php?u=https%3A%2F%2Fblog.technicalsafetybc.ca%2F9-refrigeration-safety-tips%3Futm_medium%3Dsocial%26utm_source%3Dfacebook) [![Share on LinkedIn](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/linkedin-blue.svg)](http://www.linkedin.com/shareArticle?mini=true&url=https%3A%2F%2Fblog.technicalsafetybc.ca%2F9-refrigeration-safety-tips%3Futm_medium%3Dsocial%26utm_source%3Dlinkedin) [![Share on Twitter](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/twitter-blue.svg)](https://twitter.com/intent/tweet?original_referer=https%3A%2F%2Fblog.technicalsafetybc.ca%2F9-refrigeration-safety-tips%3Futm_medium%3Dsocial%26utm_source%3Dtwitter&url=https%3A%2F%2Fblog.technicalsafetybc.ca%2F9-refrigeration-safety-tips%3Futm_medium%3Dsocial%26utm_source%3Dtwitter&source=tweetbutton&text=9%20Refrigeration%20Safety%20Tips%20%7C%20Technical%20Safety%20BC) [![Share on Email](https://blog.technicalsafetybc.ca/hubfs/raw_assets/public/technical-safety-bc/images/email-blue.svg)](mailto:?subject=Check%20out%20https%3A%2F%2Fblog.technicalsafetybc.ca%2F9-refrigeration-safety-tips%3Futm_medium%3Dsocial%26utm_source%3Demail%20&body=Check%20out%20https%3A%2F%2Fblog.technicalsafetybc.ca%2F9-refrigeration-safety-tips%3Futm_medium%3Dsocial%26utm_source%3Demail)

## Subscribe for safety updates and insights

## Browse topics

- [Homeowner](https://blog.technicalsafetybc.ca/tag/homeowner)
- [Gas](https://blog.technicalsafetybc.ca/tag/gas)
- [Contractor](https://blog.technicalsafetybc.ca/tag/contractor)
- [Electrical](https://blog.technicalsafetybc.ca/tag/electrical)
- [Asset Owner](https://blog.technicalsafetybc.ca/tag/asset-owner)
- [Ask A Safety Officer](https://blog.technicalsafetybc.ca/tag/ask-a-safety-officer)
- [Homeowner Safety](https://blog.technicalsafetybc.ca/tag/homeowner-safety)
- [Passenger Ropeways](https://blog.technicalsafetybc.ca/tag/passenger-ropeways)
- [Boiler, PV and Refrigeration](https://blog.technicalsafetybc.ca/tag/boiler-pv-and-refrigeration)
- [Carbon Monoxide](https://blog.technicalsafetybc.ca/tag/carbon-monoxide)
- [Public Safety](https://blog.technicalsafetybc.ca/tag/public-safety)
- [Amusement Devices](https://blog.technicalsafetybc.ca/tag/amusement-devices)
- [Elevating Devices](https://blog.technicalsafetybc.ca/tag/elevating-devices)
- [Railways](https://blog.technicalsafetybc.ca/tag/railways)
- [Alternative Safety Approaches](https://blog.technicalsafetybc.ca/tag/alternative-safety-approaches)
- [CO Alarm](https://blog.technicalsafetybc.ca/tag/co-alarm)
- [Client Support](https://blog.technicalsafetybc.ca/tag/client-support)
- [Smarter Safety](https://blog.technicalsafetybc.ca/tag/smarter-safety)
- [FSR](https://blog.technicalsafetybc.ca/tag/fsr)
- [Camping](https://blog.technicalsafetybc.ca/tag/camping)
- [Chairlift](https://blog.technicalsafetybc.ca/tag/chairlift)
- [Corporate news](https://blog.technicalsafetybc.ca/tag/corporate-news)
- [RV safety](https://blog.technicalsafetybc.ca/tag/rv-safety)
- [Skiing](https://blog.technicalsafetybc.ca/tag/skiing)
- [Travel](https://blog.technicalsafetybc.ca/tag/travel)
- [Vacation](https://blog.technicalsafetybc.ca/tag/vacation)
- [extreme heat](https://blog.technicalsafetybc.ca/tag/extreme-heat)
- [snowboarding](https://blog.technicalsafetybc.ca/tag/snowboarding)

## Related articles

![](https://blog.technicalsafetybc.ca/hs-fs/hubfs/Imported_Blog_Media/EscalatorSafety_smaller.jpg?width=352&name=EscalatorSafety_smaller.jpg)

### 9 Must-Know Escalator Safety Tips to Keep Your Kids Safe

 November 8, 2018

 3 Minute read

 During Elevator and Escalator Safety Awareness Week (November 9 – 15), we remind parents and caregivers of the importance of teaching kids some basic escalator safety tips and modeling safe behaviour yourself. 

[Read More](https://blog.technicalsafetybc.ca/9-must-know-escalator-safety-tips-keep-your-kids-safe?hsLang=en)

![Escalator, escalator safety tips](https://blog.technicalsafetybc.ca/hs-fs/hubfs/escalator_stock_photo-medium.jpg?width=352&name=escalator_stock_photo-medium.jpg)

### Ask a Safety Officer: Escalator Safety

 September 17, 2024

 4 Minute read

 Learn how to stay safe on escalators with expert advice from our elevating device safety officers. Discover essential tips on using escalators responsibly, from avoiding common risks to handling unexpected situations. Find answers to frequently asked questions and ensure a safer experience for everyone.

[Read More](https://blog.technicalsafetybc.ca/ask-a-safety-officer-escalator-safety?hsLang=en)

![Black excellence in technical safety](https://blog.technicalsafetybc.ca/hs-fs/hubfs/Untitled%20design%20(3).png?width=352&name=Untitled%20design%20(3).png)

### 4 Black Inventors Who Changed Technical Safety

 February 1, 2023

 4 Minute read

 4 Black inventors that improved safety across railways, electrical, elevating and BPVR and made their mark in history.

[Read More](https://blog.technicalsafetybc.ca/4-black-inventors-who-changed-technical-safety?hsLang=en)

Back to top

[Report an incident](https://portal.technicalsafetybc.ca/report-incident/incident-reporting-form)

[Contact us](https://www.technicalsafetybc.ca/contact/contact-us)

As a province-wide organization, Technical Safety BC respectfully recognizes that its employees live and work on the traditional and unceded territories of the many Indigenous Nations that have thrived throughout British Columbia since time immemorial.

[© 2026 Technical Safety BC](https://www.technicalsafetybc.ca/)

- [Cookie Policy](https://www.technicalsafetybc.ca/cookie-policy)
- [Privacy Policy](https://www.technicalsafetybc.ca/privacy-policy)
- [Terms of Use](https://www.technicalsafetybc.ca/terms-use)

<https://www.instagram.com/technicalsafetybc/?hl=en>

<https://twitter.com/techsafetybc?lang=en>

<https://ca.linkedin.com/company/technical-safety-bc>

<https://www.facebook.com/technicalsafetyBC/>

```json
{
  "@context" : "https://schema.org",
  "@type" : "BlogPosting",
  "author" : {
    "@type" : "Person",
    "name" : "Technical Safety BC",
    "url" : "https://blog.technicalsafetybc.ca/author/technical-safety-bc"
  },
  "dateModified" : "2023-12-16T00:50:16.331Z",
  "datePublished" : "2018-11-19T08:00:00.000Z",
  "headline" : "9 Refrigeration Safety Tips | Technical Safety BC",
  "image" : [ "https://blog.technicalsafetybc.ca/hubfs/Imported_Blog_Media/shutterstock_603039644-1.jpg" ],
  "mainEntityOfPage" : {
    "@id" : "https://blog.technicalsafetybc.ca/9-refrigeration-safety-tips",
    "@type" : "WebPage"
  },
  "publisher" : {
    "@type" : "Organization",
    "logo" : {
      "@type" : "ImageObject",
      "url" : "https://blog.technicalsafetybc.ca/hubfs/TSBC_Stacked_RGB%20300%20dpi%20-%20transparent%20background-1.png"
    },
    "name" : "Technical Safety BC"
  }
}
```